Pre-action device (flange)

Product overview

Product model: ZSFY

Nominal diameter: DN100-250

Rated working pressure: 1.6MPa

Seal test pressure: 3.2MPa

Connection method: flange connection

Structure: Diaphragm

Minimum working pressure: 0.25MPa

Working environment temperature: 4℃~70℃

Solenoid valve working power supply: DC24V/ 0.5A

Product standard: GB5135.14 "Automatic Sprinkler System Part 14: Pre-action Device"

Design specification: GB50084 "Specification for Design of Automatic Sprinkler System"

Acceptance Code: GB50261 "Code for Construction and Acceptance of Automatic Sprinkler System"



Product Detail

Product description

The pre-action device (flange) is the main component of the pre-action water spray system. It is composed of pre-action alarm valve group, control panel, air pressure maintaining device and air supply device. It is opened by electric or manual method, so that water can flow into the water spray system in one direction while alarming at the same time. The pre-action system combines the fire detection and sprinkler system to provide double protection for the protected object. When there is no fire, the system side pipeline is inflated, and the deluge valve seals the water on the water supply pipeline. After a fire occurs, the control center sends a start signal to the pre-action device, the pre-action device is opened, and the system is converted to a wet pipe network. It is suitable for important places where cold, freezing, high temperature, avoiding water stains, and not allowing accidental spraying of water. Such as libraries, computer rooms, underground garages in cold areas, etc.


Product size chart


预作用装置(法兰)(图1)


Main external connection size

Model

DN

A

B

D

H1

H2

φC

Bolt hole

ZSFY 100 1.6(Q-F)

100

550

360

410

610

780

180

8-φ18

ZSFY 150 1.6(Q-F)

150

550

480

485

730

880

240

8-φ23

ZSFY 200 1.6(Q-F)

200

570

508

540

885

1104

295

12-φ23

ZSFY 250 1.6(Q-F)

250

615

538

635

1105

1315

355

12-φ25